Description<br />

The <strong>Gamewell</strong> <strong>Voice</strong> (GV) <strong>Multiplexed</strong> Evacuation System<br />

<strong>Fire</strong> <strong>Command</strong> <strong>Center</strong> operates in conjunction with the <strong>600</strong><br />

<strong>Series</strong> <strong>Fire</strong> Alarm Control Panel (FACP) in a building to provide<br />

automatic response to life safety emergencies.<br />

<strong>600</strong> <strong>Series</strong><br />

<strong>Fire</strong> <strong>Command</strong> <strong>Center</strong><br />

<strong>Multiplexed</strong> <strong>Voice</strong><br />

Evacuation System<br />

The <strong>Gamewell</strong> <strong>Voice</strong> Master Panel <strong>Fire</strong> <strong>Command</strong> <strong>Center</strong><br />

includes all necessary features to provide an effective <strong>Voice</strong><br />

Evacuation and <strong>Fire</strong> Alarm Control system. The <strong>Gamewell</strong><br />

<strong>Voice</strong> Panel can be easily custom configured to satisfy the<br />

needs of any configured <strong>Voice</strong> System application.The<br />

<strong>Gamewell</strong> <strong>Voice</strong> <strong>Fire</strong> <strong>Command</strong> <strong>Center</strong> comes complete with<br />

the <strong>Gamewell</strong> RS-484 Intelligent Interface Software for communication<br />

to the <strong>Gamewell</strong> FACP. All <strong>Fire</strong> Alarm and <strong>Voice</strong><br />

Communication control are combined in a visually appealing<br />

single panel configuration.<br />

<strong>Fire</strong> Department authorities easily take command of<br />

evacuation, relocation procedures and emergencies from a<br />

single <strong>Fire</strong> <strong>Command</strong> <strong>Center</strong>. Building management and <strong>Fire</strong><br />

Brigades easily monitor and control emergency responses<br />

even before the professionals arrive.<br />

The GV system includes capacity for 6 channel digital audio.<br />

This provides for evacuation, stay-in-place, or other public<br />

address announcements and automatic messages, and<br />

fire fighter phones.<br />

<strong>Fire</strong> Fighter Phones or Warden Stations may be included<br />

as required. Smoke control, stair pressurization, and HVAC<br />

shutdown can be completely automatic, unless controlled<br />

manually by management or fire authorities, utilizing the associated<br />

<strong>Gamewell</strong> FACP.<br />

System Configuration<br />

Basic System includes:<br />

Master Panel (GV-MPXX-RC, GV-MPXXP-RC)<br />

Master Microphone Control<br />

Remote <strong>Fire</strong> Annunciation and Control<br />

Switch Control points<br />

Dual Channel Digital Message Repeator<br />

High Speed RS-485 communication loop<br />

Optional<br />

Integrated Master <strong>Fire</strong> Phone<br />

Approvals<br />

UL Listed, MEA Approved<br />

Features<br />

• True Multiplex 6 Channel Distributed Audio<br />

• Complete <strong>Fire</strong> Alarm Control Functions<br />

• Integrated <strong>Fire</strong> Phone, paging and manual EVAC<br />

• Modular System - components added as needed<br />

• Integrated 2 Channel Digital Message Repeater<br />

• Live Microphone Page to any zone<br />

• Fully Supervised<br />

• Natural Sound <strong>Voice</strong> Recordings<br />

• Built-in Alarm and Alert Signals<br />

• Up to 4 minute message capacity<br />

• All <strong>Voice</strong> control and audio data on single high speed<br />

communications loop<br />

• 3 minute message restart on microphone key<br />

• 1000 Monitor & Control Points<br />

CS-2176 09/01/06<br />

Page 1


Specifications<br />

Primary Power:<br />

Electrical Ratings<br />

Communications Bus:<br />

Voltage:<br />

Current:<br />

Impedance:<br />

Frequency:<br />

Backbox Dim:<br />

Color:<br />

120 VAC 24 VDC Battery Power<br />

(All Circuits @ 24VDC.)<br />

RS-485 Standard, 1M Baud data rate, Category 5 cable.<br />

5V peak-to-peak max.<br />

50mA max.<br />

120 Ohms (max. imp. between panels)<br />

1.024MHz<br />

14.5 x 27 x 4“ w h d<br />

RED - standard<br />

Master Panel Components:<br />

Standby Alarm Standby Alarm<br />

GV-DCC 80 mA 80 mA GV-SLC 6 ma 6 ma<br />

GV-ASC 30 mA 30 mA GV-MMC 45 ma 45 ma<br />

GV-MFP 10 mA 10 mA GV-I/O cards 20 ma 20 ma<br />

GV-SSC 25 mA 25 mA<br />

Ordering Information<br />

Master Panel <strong>Fire</strong> <strong>Command</strong> <strong>Center</strong> Configurations<br />

GV-MP16-RC Master Panel, 16 Switch Control, Remote <strong>Fire</strong> Contol<br />

GV-MP32-RC Master Panel, 32 Switch Control, Remote <strong>Fire</strong> Contol<br />

GV-MP48-RC Master Panel, 48 Switch Control, Remote <strong>Fire</strong> Contol<br />

GV-MP64-RC Master Panel, 64 Switch Control, Remote <strong>Fire</strong> Contol<br />

GV-MP80-RC Master Panel, 80 Switch Control, Remote <strong>Fire</strong> Contol<br />

GV-MP96-RC Master Panel, 96 Switch Control, Remote <strong>Fire</strong> Contol<br />

GV-MP112-RC Master Panel, 112 Switch Control, Remote <strong>Fire</strong> Contol<br />

GV-MP128-RC Master Panel, 128 Switch Control, Remote <strong>Fire</strong> Contol<br />

GV-MP144-RC Master Panel, 144 Switch Control, Remote <strong>Fire</strong> Contol<br />

GV-MP16P-RC<br />

GV-MP32P-RC<br />

GV-MP64P-RC<br />

GV-MP80P-RC<br />

GV-MP96P-RC<br />

GV-MP112P-RC<br />

GV-MP128P-RC<br />

Master Panel, 16 Switch Control, Master <strong>Fire</strong> Phone, Remote <strong>Fire</strong> Contol<br />

Master Panel, 32 Switch Control, Master <strong>Fire</strong> Phone, Remote <strong>Fire</strong> Contol<br />

Master Panel, 64 Switch Control, Master <strong>Fire</strong> Phone, Remote <strong>Fire</strong> Contol<br />

Master Panel, 80 Switch Control, Master <strong>Fire</strong> Phone, Remote <strong>Fire</strong> Contol<br />

Master Panel, 96 Switch Control, Master <strong>Fire</strong> Phone, Remote <strong>Fire</strong> Contol<br />

Master Panel, 112 Switch Control, Master <strong>Fire</strong> Phone, Remote <strong>Fire</strong> Contol<br />

Master Panel, 128 Switch Control, Master <strong>Fire</strong> Phone, Remote <strong>Fire</strong> Contol<br />

For systems requiring more switch controls then indicated above please contact <strong>Gamewell</strong> Corporate Marketing.<br />

All systems require Distributed Panels (DP) for operation.<br />

Panel Options: Cards may be added as job requirements demand<br />

GV-MFP Master <strong>Fire</strong> Phone Enables system to incorporate 2 way communication. Included with “P” panels.<br />

GV-MMC-RC Master Mic & RAN/RC Master Microphone Control & <strong>Gamewell</strong> RAN2-RC with mounting Place.<br />

GV-SSC Switch Scan Card Included in basic panels, up to 7 additional cards may be added.<br />

GV-SLC Switch LED Card 16 LED Switch Bank card, up to 8 per GV-SSC.<br />

GV-IIC Input Interface card 16 FACP input card. Provides hard wire interface to FACP. (128 pts max)<br />

GV-OI Output Interface Card 16 FACP output card. Provides hard wire interface. (128 pts max)<br />

Custom messages available. Please contact factory.<br />

Specifications and wiring information are provided for information only and are believed to be accurate. <strong>Gamewell</strong>-FCI assumes no<br />

responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the<br />

product shall always be used for actual installation. For more information, contact <strong>Gamewell</strong>-FCI.<br />

<strong>Gamewell</strong>-FCI Tel: (203) 484-7161<br />

12 Clintonville Road FAX: (203) 484-7118<br />

Northford, CT 06472<br />

www.gamewell-fci.com<br />

©<strong>Gamewell</strong>-FCI 2006<br />

CS-2176 09/01/06<br />